PPL-630-A
Differential Pressure Switches

Description

Ideal for flow monitoring and proving applications in heating, ventilating and air-conditioning systems.

Features

- Over-pressure safety capability to 10 bar (145 psi) / 20 bar (290 psi)
- Mechanically isolated switching chamber for safety and reliability
- Medium temperatures to 80°C (176°F)
- Rugged construction
- Adjustable setting and differential
Specifications

SPECIFICATIONS

Max. operating pressure and overload on one side (P1> P2): With range ≤ 200 mbar (2,9 psi) = 10 bar (145 psi)
With range 150-5000 mbar (2,2-72,5 psi) = 20 bar (290 psi)
Lowest turn-on pressure: 15 mbar
Pressure connection: ⅛ "BSP female
Ambient: Water, air, steam (with pig tail)
Electrical rating: 1A (0,5) @ 250Vac
Operating range: -10 to 80 ° C (14 to 176 ° F)
Protection: IP65
Dimensions: 110 x 65 mm
Weight: 1,08 kg

 

Models & Accessories
CODE DESCRIPTION
Output 4-20 mA
PPL-630-A-0.026 to 20 mbar (0,1 to 0,3 psi) Liquid Diff Pressure Switch
PPL-630-A-0.0615 to 60 mbar (0,2 to 0,9 psi) Liquid Diff Pressure Switch
PPL-630-A-0.240 to 200 mbar (0,6 to 2,9 psi) Liquid Diff Pressure Switch
PPL-630-A-10,15 to 1 bar (2,2 to 14,5 psi) Liquid Diff Pressure Switch
PPL-630-A-31 to 3 bar (14,5 to 43,5 psi) Liquid Diff Pressure Switch
PPL-630-A-5.52 to 5,5 bar (29 to 79,8 psi) Liquid Diff Pressure Switch
Download

Datasheet

To download the product datasheet, please click the links below:

Pulpit rock