PTT-518
Thimble Sensors

Description

Thimble temperature sensors are used for measuring air temperature in indoor spaces. Units contain either a high quality thermistor, Nickel or Platinum sensing element. The sensing element is mounted in an attractive ‘thimble’ enclosure for surface mounting, typically on a backplate or a ceiling tile.
Features

- Plastic, brass, stainless steel or aluminium thimble options
- Note: If no colour is specified, standard off-white thimble will be supplied.
Specifications

SPECIFICATIONS

Output types:Thermistor Resistive
 Current 4 to 20 mA
 Voltage 0 to 10Vdc
Thread: Plastic M16x1.5x25mm
  All others M16x1.5x12mm
Connections:2m flying lead, screened
Ambient range:-10 to +60 ° C
Protection:IP30
Dimensions:Plastic 45mm overall x 22mm dia.
Metal 30mm overall x 19mm dia.
Weight:80 g
Models & Accessories
CODE DESCRIPTION
Passive Output
PTT-518-A10K3A1, Trend, Seachange, Cylon, Distech
PTT-518-B10K4A1, Andover
PTT-518-C20K6A1, Honeywell
PTT-518-DPT100A, Serck
PTT-518-EPT1000A, Cylon
PTT-518-FNi1000A, Sauter
PTT-518-GNi1000A/TCR (LAN1), Siemens
PTT-518-HSAT1, Satchwell
PTT-518-LTAC1, TAC
PTT-518-M2,2K3A1, Johnson Controls
PTT-518-N3K3A1, Alerton
PTT-518-P30K6A1, Drayton
PTT-518-Q50K6A1, Ambiflex
PTT-518-R100K6A1, York > 40ºC
PTT-518-SSAT2, Satchwell
PTT-518-TSAT3, Satchwell
PTT-518-WSIE1, Siebe
PTT-518-YSTA2, Landis & Staefa
PTT-518-Z10K NTC, Carel
PTT-518-DCDelta Controls
Active Output
PTT-518-CVO4-20mA/0-10 Vdc selectable output,
Output ranges:
-10 to + 40ºC or
-10 to 110º C
PTT-518-CVO-C4-20mA/0-10 Vdc selectable output,
Specific calibration in the range of:
-30 to 60º C
Suffixes
-ALAluminum thimble
-SSStainless Steel thimble
-BRBrass thimble
-BWBrilliant white thimble
-5M5m cable lenght
Download

Datasheet

To download the product datasheet, please click the links below:

Pulpit rock